Circuit Breaker
Services

|
- Circuit Breakers 208V- 34.5kV
|
- Repairs/Rebuilds/Recondition
|
|
|
|
|
- Inspection and Maintenance
|
|
|
| High Energy Electric, Inc.
offers factory trained field representatives for Federal Pacific Electric (FPE),
Allis-Chalmers (A-C), Siemens-Allis and Siemens products. In addition, our
technicians attend schools and seminars available to them from most manufacturers.
If we cannot locate an obsolete part or component, the device will be fabricated, to
factory specifications, at one of our local machine shops. |
| Several of our recent projects included
the reconditioning and retrofitting of a switchgear line-up of GE type AE and AK
circuit breakers. The AK breakers were in very poor condition, some breakers were
frozen in the closed position. The units were complete disassembled and rebuilt,
tested and installed. Aside from a few short scheduled shutdowns, the customer did
not lose any production time. High Energy Electric, Inc. had provided spare circuit
breakers that were interchanged as needed. Another project undertaken this year was
to perform the 10 year interval inspection on 3 Siemens type SP sulfur Hexaflouride SF6
breakers. Our technicians evacuated the gas into an approved container, dismantled
the switch and contact structure, cleaned and reassembled the unit. Prior to
reenergization, an A-C hipotential, a D-C insulation resistance and contact resistance
tests were performed. The circuit breaker was reenergized prior to our departure. |
 The
above picture shows GE-AK circuit breakers before and
after being reconditioned. |
| High Energy Electric, Inc.
maintains a large array of circuit breaker testing equipment. Test currents range
from .1 amp to 6,000 amps. Testing can be performed at our facility or yours, 24
hours a day, 7 days a week. Each piece of equipment is calibrated and traceable to
NIST standards. |
Home Page
Services Equipment
Rentals Items For Sale Employment
Opportunities

High Energy Electrical
Testing, Inc.
Phone: 732-286-4088
Fax: 732-286-4086 |